Type 1+2 PV Surge Protective Device TRS8 1500v
Main Features
- Lightning impulse current(10/350μs) limp: 5kA/7kA
- Nominal discharge current (8/20μs) In: 20kA
- Maximum discharge current (8/20μs) Imax: 40kA
- Network Systems: (+)-PE, (-)-PE, (+)-(-)
- IEC/EN Category: Type 1+2 / Class I+II / Class B+C
- Protective Elements: High Energy MOV
- Housing: Pluggable design
- Application: String box, Inverter
- Compliance: EN 61643-31:2012, IEC 61643-31:2011

The TRS8-DC1500 is a high-performance Type 1+2 DC surge protective device engineered for modern photovoltaic (PV) power systems operating up to 1500 VDC.
Combining MOV and GDT hybrid protection technology, it delivers strong lightning-current handling capability along with a stable clamping response, making it suitable for both rooftop PV installations and large-scale solar plants.
This device is designed to withstand demanding electrical environments where both direct lightning impulses and switching surges can pose risks to PV strings, inverters, and DC distribution equipment.
Its integrated visual fault indicator provides clear status feedback, while optional potential-free remote signaling contacts support system-wide monitoring and automated fault reporting.
Built for long-term reliability, the TRS8-DC1500 performs effectively across a wide temperature range and maintains consistent surge protection even under high DC voltage stress.
The compact housing and DIN-rail mounting structure ensure easy installation inside combiner boxes, inverter cabinets, and DC control panels.
Applications
High-voltage photovoltaic systems operating up to 1500 VDC
Utility-scale solar farms requiring Type 1+2 combined lightning and surge protection
PV combiner boxes, inverter DC inputs, and DC distribution enclosures
Installations exposed to frequent lightning activity or harsh outdoor environments
Systems requiring visual fault indication and optional remote monitoring
Projects that demand a hybrid MOV+GDT device for enhanced surge durability
| Parameter/Type | TRS8-DC1500 |
|---|---|
| Max. PV Operating Voltage Ucpv | 1500V DC |
| Lightning impulse current(10/350µs) Imp | 5kA |
| Nominal discharge current (8/20µs) In | 20kA |
| Maximum discharge current (8/20µs) Imax | 40kA |
| Voltage protection level mode +/PE, -/PE Up | ≤5.2kV |
| Short-circuit current rating Iscpv | 10kA |
| Response time ta | < 25ns |
| Cross-section of connected conductors solid(min/max) | 16mm²/35mm² |
| Cross-section of connected conductors stranded(min/max) | 16mm²/35mm² |
| Fault indication | red indication field |
| Remote indication | potential-free change-over contact |
| Remote indication contacts | 250V/0.5A AC, 250V/0.1A DC |
| Cross-section of remote indication conductors | 1.5mm² |
| Degree of protection | IP20 |
| Range of operating temperatures (min/max) | -40℃~+85℃ |
| Humidity range | 5%~95% |
| Mounting | DIN rail 35 mm |
| According to standard | EN61643-31:2012, IEC61643-31:2011/T1+T2 |
| Remarks | Other Ucpv can be customized.(1200VDC, 1500VDC, etc.) |



Related Products
| Uocstc | 1000v, 1250v |
|---|---|
| Ucpv | 1200v, 1500 |
| Iimp | 5kA, 7kA |
| Z0 | 50 Ohm |
|---|---|
| IL | ≤0.3dB |
| Freq. | DC-2.5GHz |
| VSWR | <1.2 |
| Uocstc | 110v, 24v, 48v, 75v |
|---|---|
| Ucpv | 180v, 36v, 65v, 80v |