Type 2 DC Surge Protective Device TRS2-DC
Main Features
- Nominal discharge current (8/20μs) In: 20kA
- Maximum discharge current (8/20μs) Imax: 40kA
- Network Systems: (DC+)-PE, (DC-)-PE
- IEC/EN Category: Type 2 / Class II
- Protective Elements: High Energy MOV
- Housing: Pluggable design
- Application: DC distribution, Industrial control panels, Telecom systems
- Compliance: EN 61643-31:2012, IEC 61643-31:2011



The TRS2-DC is a Type 2 DC surge protective device (SPD) designed for low-voltage DC power systems. With a maximum continuous operating voltage (Uc) of 150V DC, it provides protection against transient overvoltages caused by switching operations and indirect lightning effects.
Featuring MOV-based surge protection technology, the TRS2-DC delivers a nominal discharge current (In) of 20kA and a maximum discharge current (Imax) of 40kA under the 8/20μs waveform.
Its voltage protection level (Up) of ≤0.5kV helps limit transient overvoltages and protect sensitive electronic components in DC distribution and industrial control systems.
The compact pluggable design allows for convenient module replacement and maintenance, while standard 35mm DIN rail mounting simplifies installation within electrical cabinets and equipment enclosures.
A visual fault indicator allows users to check the operating status of the SPD. Optional potential-free remote signaling contacts enable integration with equipment monitoring systems.
With an operating temperature range of -40°C to +70°C and an IP20 protection rating, the TRS2-DC is suitable for installation inside industrial electrical cabinets and DC distribution panels.
Applications
DC auxiliary power circuits in EV charging equipment and energy storage systems (ESS).
DC power supply protection in telecommunications infrastructure.
Industrial automation and control panels.
Low-voltage DC distribution cabinets.
Sensitive electronic equipment requiring a low voltage protection level.
| Parameter/Type | TRS2-DC | |
|---|---|---|
| Maximum continuous operating voltage | Uc | 150V DC |
| Max. PV Operating Voltage | Ucpv | |
| Nominal discharge current (8/20µs) | In | 20kA |
| Maximum discharge current (8/20µs) | Imax | 40kA |
| Voltage protection level mode +/PE, -/PE | Up | ≤0.5kV |
| Short-circuit current rating | Iscpv | 10kA |
| Response time | ta | < 25ns |
| Cross-section of connected conductors solid(min/max) | 16mm²/35mm² | |
| Cross-section of connected conductors stranded(min/max) | 16mm²/35mm² | |
| Fault indication | red indication field | |
| Remote indication | potential-free change-over contact | |
| Remote indication contacts | 250V/0.5A AC, 250V/0.1A DC | |
| Cross-section of remote indication conductors | 1.5mm² | |
| Degree of protection | IP20 | |
| Range of operating temperatures (min/max) | -40℃~+70℃ | |
| Humidity range | 5%~95% | |
| Mounting | DIN rail 35 mm | |
| According to standard | IEC 61643-11/T2 | |
Rotate the 3D model to inspect the surge protective device from different angles. For detailed technical specifications, electrical ratings and installation information, please refer to the other tabs.
Related Products
| Uc | 275v, 320v, 385v, 420v |
|---|---|
| Iimp | 15kA |
| Uocstc | 1000v, 1250v |
|---|---|
| Ucpv | 1200v, 1500 |
| Iimp | 5kA, 7kA |
| Z0 | 50 Ohm |
|---|---|
| IL | ≤0.3dB |
| Freq. | DC-2.5GHz |
| VSWR | <1.2 |