Type 2 AC Surge Protective Device TRS6-B100
Main Features
- Nominal discharge current (8/20μs) In: 60kA
- Maximum discharge current (8/20μs) Imax: 100kA
- Network Systems: TN-S, TT
- Mode of Protection: L-PE, N-PE
- IEC/EN Category: Class II / Type 2
- Protective Elements: High Energy MOV
- Housing: Pluggable design
- Application: Sub-Distribution Board
- Compliance: EN 61643-11:2012, IEC 61643-11:2011/T2

The TRS6-B100 is a high-capacity Type 2 surge protective device developed for applications requiring stronger surge endurance and enhanced system resilience.
Based on advanced MOV technology, it provides dependable protection for main distribution boards and electrical environments subjected to higher transient energy levels.
Built with a non-pluggable, fully integrated housing, the TRS6-B100 delivers excellent structural stability and long-term durability.
Its clear red fault indicator enables quick on-site assessment, while optional potential-free signaling contacts make it easy to connect the device to supervisory or warning systems.
With a rugged construction and DIN-rail mounting design, the TRS6-B100 ensures efficient installation and reliable performance across residential, commercial, and light-industrial electrical networks.
Applications
Main and sub-distribution boards requiring increased surge handling capability
Commercial buildings and light-industrial facilities
Electrical systems frequently exposed to switching transients or elevated surge activity
Setups requiring visual fault indication and optional remote signaling
AC distribution solutions demanding durable and long-lasting surge protection
| Model | TRS6-B80 | TRS6-B100 | ||
| Nominal volatge (Un) | 380 V AC | |||
| Maximum operating voltage (Uc) | 385 V AC | |||
| Nominal discharge current (8/20μs) (In) | 40 kA | 60 kA | ||
| Maximum discharge current (8/20μs)(Imax) | 80 kA | 100 kA | ||
| Voltage protection level (Up) | ≤ 2,4 kV | ≤ 2,5 kV | ||
| Response time (ta) | < 25ns | |||
| Cross-section of connected conductors solid (min/max) | 16 mm2 / 35 mm2 | |||
| Cross-section of connected conductors stranded (min/max) | 16 mm2 / 35 mm2 | |||
| Fault indication | red indication field | |||
| Remote indication | potential-free change-over contact | |||
| Remote indication contacts | 250 V / 0,5 A AC, 250 V / 0,1 A DC | |||
| Cross-section of remote indication conductors | 1,5 mm2 | |||
| Degree of protection | IP20 | |||
| Range of operating temperatures (min/max) | -40℃~+70℃ | |||
| Humidity range | 5%~95% | |||
| Mounting | DIN rail 35 mm | |||
| According to standard | EN 61643-11:2012, IEC 61643-11:2011 / T2 | |||
| Remarks | Other Uc can be customized.(420V AC, 275V AC, 320V AC, etc.) | |||




Related Products
| Uocstc | 1000v, 1250v |
|---|---|
| Ucpv | 1200v, 1500 |
| Iimp | 5kA, 7kA |
| Z0 | 50 Ohm |
|---|---|
| IL | ≤0.3dB |
| Freq. | DC-2.5GHz |
| VSWR | <1.2 |
| Uocstc | 110v, 24v, 48v, 75v |
|---|---|
| Ucpv | 180v, 36v, 65v, 80v |