In a 3+1 SPD, the N-PE module is a spark gap because it has a different job from the three L-N modules. It carries the combined discharge current of all four conductors, it has to stay open through overvoltages between neutral and earth that would destroy an MOV, and its failure mode has to be open rather than short. That last point is why a TT installation with the SPD ahead of the RCD calls for exactly this arrangement.
If you need the wiring comparison first, see 4+0 and 3+1 configuration. This article is about the fourth module only.
What the N-PE module does in a 3+1 SPD
In a 3+1 arrangement, the three L-N paths do the first job: each MOV clamps its phase to neutral. The N-PE module does the second: it takes everything that has arrived at neutral and returns it to earth.
That makes it a return path, not a fourth phase protector. During a common-mode surge, current arrives on all four conductors. The three phases pass theirs through the L-N MOVs into the neutral bar, the neutral conductor brings its own share, and all of it leaves through the N-PE module to the earthing system. If the N-PE module does not conduct, the L-N MOVs have nowhere to send the current they have just clamped.

Figure 1 — In a 3+1 SPD, the three L-N MOVs clamp each phase to neutral; the N-PE spark gap returns the combined current to earth.
alt text: 3+1 SPD circuit showing three L-N MOV paths and one N-PE spark gap path to earth
It carries the combined current
The N-PE module sees the total, not one conductor’s share. If a lightning partial current splits evenly across L1, L2, L3 and N at 12.5 kA each, the N-PE element carries 50 kA.
That is why the N-PE module in a 3+1 assembly is rated several times higher than a phase module, and why the common-mode rating of the whole assembly is set by that one element. You cannot read the N-PE rating off the L-N module next to it. If you are sizing the assembly, how to size an SPD covers the sum and the waveform.
Spark gap surge protection suits that duty. An MOV absorbs surge energy in the bulk of its zinc-oxide disc, so a disc big enough for the full 10/350 µs sum is large and still ages with every operation. A gap passes the current through an arc that drops only tens of volts, so it dissipates far less energy and a compact module can carry the total. For the component-level explanation, see gas discharge tube. A GDT belongs to the same voltage-switching family and the argument applies to it.
Neutral is not always at earth potential
In a TN-S or TN-C-S installation, N and PE are bonded at the origin, so the voltage between them stays low in normal service. That is why a 4+0 SPD with MOVs on every pole works there, and we will come back to it.
A TT installation is different. The neutral is earthed at the source, the protective earth is your own electrode, and the two are not bonded. In normal service the difference is a few volts. During an earth fault in the installation, the local PE rises by the fault current times the electrode resistance, close to the phase voltage in the worst case. If the neutral is lost on an unbalanced three-phase supply, N drifts towards one of the phases and can sit near 230 V against the local earth until the fault is found.
Those voltages are within the continuous rating of a 255 V module, gap or MOV. The voltage that decides the technology comes from a fault on the high-voltage side of the supply transformer. That fault current flows through the substation earth, lifts the LV neutral against your local earth, and puts well over a kilovolt across N-PE for a fraction of a second. SPD standards test N-PE modules for TT systems at 1,200 V for 200 ms. A gap built for the N-PE position rides through that and returns to open. An MOV with a 255 V Uc cannot; it conducts hard, overheats and fails.
The failure mode is the deciding argument
An MOV at the end of its life fails short, and where it sits decides what that short does.
In a TT installation the earth-fault current has to return through two electrodes, so it is small, often a few amps. Put a 4+0 SPD ahead of the RCD and let one L-PE MOV fail short. The phase is now connected to PE, the fault current is too small to trip the overcurrent device, the RCD is downstream and never sees it, and the exposed metalwork of the installation sits at a dangerous touch voltage until someone finds it. That is why IEC 60364-5-53 requires an SPD installed upstream of the RCD in a TT system to use connection type 2: L-N modules plus an N-PE module, which is the 3+1. A failed L-N MOV is then a phase-neutral short, and the overcurrent device clears it at once.

Figure 2 — In a TT system, a shorted L-PE module ahead of the RCD leaves the metalwork live; in a 3+1, the same failure is a phase-neutral short that the overcurrent device clears.
That argument only works if the N-PE element is a gap. An N-PE MOV that fails short is a permanent neutral-earth link ahead of the RCD. The installation stops being TT, part of the neutral current returns through the earth electrode, and the protection is gone without anything tripping. A spark gap normally fails open: you lose the N-PE path and the protection, but you do not add a conductor that was not there before. The TT earthing system article covers the fault path in more detail.
Gaps can still fail short, and one that has been through many operations behaves differently from a new one. Wire the status indicator or remote signalling contact on the N-PE module rather than relying on a yearly look.
It keeps the L-PE residual voltage lower
In a 3+1 SPD, an L-PE surge passes through two elements in series: the L-N MOV and the N-PE element. The L-PE voltage the equipment sees is the sum of what both drop at each moment.
With a gap there are two moments. Before it fires, almost no current flows, so the L-N MOV drops little and the gap holds its sparkover voltage. Once the arc forms, the gap drops only tens of volts and the L-N MOV takes the current at its clamping voltage. The L-PE Up is the higher of those two peaks, so it is set mainly by the gap’s sparkover, not by two residual voltages added together.
With an MOV in the N-PE slot there is no handover. Both MOVs carry the full current at the same time and their residual voltages add. Take a 1.3 kV L-N module and a 1.2 kV N-PE MOV, and the equipment sees about 2.5 kV L-PE.
| Configuration | L-PE path during a surge | L-PE residual voltage |
| 3+1, spark gap N-PE | L-N MOV in series with the gap | Gap sparkover before firing; L-N Up plus tens of volts after |
| 3+1, MOV N-PE | L-N MOV in series with the N-PE MOV | L-N Up + N-PE Up |
| 4+0, MOV L-PE | One L-PE MOV | L-PE Up |
Manufacturers state the L-PE Up of a 3+1 assembly as its own figure. Read that value from the datasheet rather than building it from the module ratings.

Figure 3 — L-PE residual voltage in a 3+1 SPD: a gap N-PE is limited by its sparkover, then drops to tens of volts; an MOV N-PE adds a second full Up.
When a 4+0 MOV N-PE is fine
None of this makes 3+1 universally better. In TN-S and TN-C-S, N and PE are tied at the origin, the N-PE voltage stays low, and an earth fault is a low-impedance fault that the overcurrent device clears. A 4+0 SPD with MOVs on all four poles is simple, uses one module type, and gives a direct L-PE path with no series element.
| Earthing arrangement | N-PE voltage in service | Common choice |
| TT | Rises during earth faults and HV-side faults; N can drift if the neutral is lost | 3+1 with a spark gap N-PE, required ahead of the RCD |
| TN-S | Low: N and PE bonded at the origin | 4+0 with MOVs, or 3+1 |
| TN-C-S (PME) | Low at the installation: a PEN break upstream lifts N and PE together | 4+0 with MOVs is common |
| IT | No earthed neutral; the first earth fault leaves phases at line voltage to PE | Modules from each live conductor to PE, rated for line voltage |
A PEN break in TN-C-S is often quoted as an N-PE overvoltage, but it is not one: the break is upstream of the N-PE bond, so neutral and protective earth rise together and the voltage between them stays low. What rises is the potential of both against true earth, and that is an L-PE problem for the SPD, not an N-PE one. The N-PE element is exposed where the two are separately earthed, which is TT.
On site: testing and replacement
Insulation resistance is tested with the SPD disconnected, or at a reduced 250 V where disconnecting it is not practical. If an L-PE or N-PE reading comes out low with the SPD still connected, suspect the SPD before the wiring: disconnect it and test again.
Replacement is where the wrong part gets fitted. The N-PE cartridge and the phase cartridges often share a footprint and a base, but the N-PE cartridge is a gap rated for the combined current, and a spare L-N cartridge is an MOV rated for one conductor’s share. Clipped into the N-PE slot, it brings back every problem in this article. Order the N-PE cartridge by its own part number.
Choosing a 3+1 SPD
Four inputs settle it: the earthing arrangement, the Uc the phase modules need for your supply, the impulse current the N-PE module must carry, and the assembly’s L-PE Up against what the equipment can withstand. Read the N-PE module’s ratings as a separate line on the datasheet, not as a copy of the phase module’s.
For TT supplies we build the TRS5 Type 1+2 SPD as a 3+1 with a GDT N-PE module. In the 385 V version, each phase module is rated Iimp 7 kA with Up ≤1.8 kV, and the N-PE module is rated Uc 255 V, Iimp 25 kA and Up ≤1.2 kV, about three and a half times the phase rating. Take the remote signalling option on a 3+1; it is the easiest way to know the N-PE module is still there.

Figure 4 — Thor TRS5 Type 1+2 SPD, 385 V version, in a 3+1 arrangement with an N-PE module.
FAQ
Can a 3+1 SPD be used on an IT system?
No. An IT system has no earthed neutral, and after the first earth fault the healthy phases sit at line voltage against PE until the fault is found. The SPD modules therefore go from each live conductor to PE and are rated for line voltage. A 3+1 with a 255 V N-PE module and phase-voltage L-N modules does not fit that; use the manufacturer’s IT configuration.
Why is the N-PE module marked 255 V when the phase modules are 275 V or 385 V?
Uc is the maximum continuous voltage for the module’s own position. For the N-PE position the installation standard sets the minimum from the nominal phase-to-earth voltage, and 255 V clears it for a 230 V system. The phase modules are chosen for their position, at 275 V or 385 V depending on how much supply overvoltage they must ride through. The numbers are not a ranking: a 275 V L-N cartridge is the wrong part in the N-PE slot because it is an MOV with a fraction of the current rating, not because of its voltage.
Does a spark gap N-PE cause RCD nuisance tripping?
No. At mains voltage the gap is open and passes no current, so it adds nothing to the residual current the RCD measures. It conducts only during a surge or an HV-side fault, for microseconds to milliseconds. Repeated tripping points to a shorted N-PE element or an earth fault elsewhere in the installation.
Specify a 3+1 SPD for your earthing system
Tell us the earthing arrangement, the system voltage, the surge current you need to handle, and whether an RCD sits upstream of the SPD. We will confirm the L-N and N-PE modules as a pair, because the ratings are not interchangeable and the assembly’s common-mode performance depends on both. Start with the AC surge protection device range.